WBIO-DO-R10A-8 Relay Module
Application
Suitable for switching incandescent lighting and motors.
For information on choosing a relay module, see Recommendations for selecting a relay for a load.
Technical specifications
| Parameter | Value |
|---|---|
| Number of outputs | 8 |
| Output type | Mechanical relay |
| Contact configuration | SPST, normally open
States:
|
| Maximum switching voltage (AC) | 250 V |
| Maximum switching voltage (DC) | 30 V |
| Maximum switching current per channel (*) | 7 A |
| Maximum DC switching current per channel | 10 A |
| Channel resistance (open) | < 100 mΩ |
| Напряжение изоляции между катушкой реле и контактами | 4000 VAC (1 мин) |
| Напряжение изоляции между разомкнутыми контактами реле | 1000 VAC (1 мин) |
| Service life: number of switching operations
for 10 A, 230 V AC load, cos φ = 1 |
100,000 |
| Module type | "O" (non-inverted address scheme) |
| Maximum power consumption | 1.15 W (2.5 W peak) |
| Operating conditions | |
| Ambient temperature | From −40 to +80 °C |
| Relative humidity | Up to 95%, non-condensing |
| Climatic rating according to GOST 15150-69 | O2.1* |
| Warranty period | 2 years |
| Service life | 5 years |
| Compatibility | |
| Controller compatibility | Wiren Board 5, 6, 7, 8 |
| Module compatibility | Interface modules WB-MIO and WB-MIO-E |
| Terminal blocks and wire cross-section | |
| Recommended wire cross-section with ferrules | 0.5–2.5 mm2 |
| Standard ferrule length | 8 mm |
| Screw tightening torque | 0.5 N·m |
| Dimensions | |
| Width, DIN units | 3 |
| Overall dimensions (L × W × H) | 53 × 90 × 58 mm |
| Weight (with packaging) |
160 g |
* Maximum switching current is specified for a resistive load at 230 V AC.
Operating principle
Contains 8 HF32F-G relays manufactured by Hongfa (Datasheet), with SPST contact configuration (two contacts per relay: NO/COM), each switching a corresponding output. The outputs are routed to screw terminals.
Current up to 7 A per channel. Depending on the hardware revision, each relay contact may be equipped with a varistor for overvoltage protection.
Installation
I/O modules are connected to the Wiren Board controller or the WB-MIO interface converter on the right side via the side connector. Make sure all module pins are properly aligned with the mating connector.
Secure the modules on the DIN rail using end stops on both sides, but leave approximately 2 cm of free space for easy removal when needed.
You can connect up to 8 modules in total: up to 4 input modules (type “I”) and up to 4 output modules (type “O”). Exception: only one WBIO-AI-DV-12 module can be connected.
Addresses are assigned sequentially. You can connect up to 4 modules in any order. If connecting more than 4, group modules by type: connect all of one type first, then the other.
Load connection
Relays are connected in series with the phase conductor.
Controller connection setup
General information
After physically connecting the module, it must be added to the controller configuration:
- In the web interface, go to Settings → Configuration files.
- Open the Extension modules and ports section and select the WBIO module (External I/O module) where the side-mounted WBIO module is connected.
- In the dropdown list Module type, select the type of the connected module.
- Click the Save button.
To remove a module, select the Not installed type.
Make sure the external module is visible in the web interface:
- Go to the Devices section.
- Find the Relays & FETs device (or Discrete I/O on Wiren Board 6 and earlier) for digital modules, or ADCs for analog modules. The channels will appear as EXTN_YYYY, where N is the module number and YYYY is the channel name.
The MQTT topic will be of the form /devices/wb-gpio/controls/EXTN_YYYY.
Module-specific features
Web interface appearance
In the Module type field, select the device WBIO-DO-RxA-8: 8 Channel Relay I/O module.
In the web interface, the relays will appear as controls EXTx_R3A1 to EXTx_R3A8 of the Discrete I/O device.
MQTT topic names: /devices/wb-gpio/controls/EXTx_R3Ay.
Unused output
One output on each side of the device is not used.
Device revisions
The batch number can be found on a sticker on the side of the case or on the PCB.
| Revision | Batch | Release date | Differences from previous revision |
|---|---|---|---|
| 3.2 | v3.2A, v3.2B | 05.2025 – ... |
|
| 2.6 | v2.6C | 10.2024 – 05.2025 |
|
| 2.6 | v2.6A, v2.6B | 11.2023 – 10.2024 |
|
| 2.5 | v2.5L | 09.2023 |
|
| 2.5 | v2.5E, v2.5F, v2.5G, v2.5H, v2.5I, v2.5J, v2.5K | 10.2021 – 02.2023 |
|
| 2.5 | v2.5A, v2.5B, v2.5C, v2.5D | 12.2020 – 10.2021 |
|
| 2.4 | v2.4A – v2.4M | 09.2019 – 03.2021 |
|
| 2.2 – 2.3 | 225, 279, 311, 330, v2.3A | 04.2018 – 09.2019 |
|
| 2.2 | 168 | Summer 2017 |
|
| 2.0 – 2.2 | ??, 168/G, 190, 206 | Until 02.2018 |
|
| 1.2 | ?? | Until 2016 |
|
Device images and drawings
Corel Draw 2018 (font — Ubuntu): Файл:WB-Library.cdr.zip
Visio:
- Wiren Board devices: Файл:WB-Visio-Lib.zip.
- Panels, circuit breakers, contactors, and more by a third-party developer.
SVG: Файл:WBIO-DO-R10A-8.svg.zip
Autocad 2013 DXF: Файл:WBIO-DO-R10A-8.dxf.zip
Autocad PDF: Файл:WBIO-DO-R10A-8.pdf