Digital Output Module WBIO-DO-HS-8

The model is discontinued. Recommended replacement: WBIO-DO-SSR-8.
Purpose
The module is designed to control low-voltage loads: relays, low-voltage motors, signal lamps, etc.
Technical specifications
| Parameter | Value |
|---|---|
| Number of outputs | 8 |
| Number of groups | 1 |
| Output type | High Side Switch |
| Switched voltage | 11 - 45 V DC |
| Maximum switched current (per channel) | 0.6 A |
| Leakage current through an off output (per output) | <10 µA |
| On-state channel resistance | 200 mOhm |
| Module type | O (non-inverted addr.) |
| Maximum power consumption | 0.025 W |
| Operating conditions | |
| Ambient temperature | From −40 to +80 °C |
| Relative humidity | Up to 95%, non-condensing |
| Climatic rating according to GOST 15150-69 | O2.1* |
| Warranty period | 2 years |
| Service life | 5 years |
| Terminal blocks and wire cross-section | |
| Recommended wire cross-section with a sleeve terminal | 0.35 – 1 mm2 — single, 0.35 – 0.5 mm2 – double crimping |
| Length of a standard sleeve terminal | 8 mm |
| Screw tightening torque | 0.2 N∙m |
| Dimensions | |
| Width, DIN units | 2 |
| Overall dimensions (L x W x H) | 36 x 90 x 58 mm |
| Weight (with packaging) |
80 g |
General operating principle
The module has 8 "High Side Switch" outputs: when a channel is turned on, the Vin voltage is applied to its terminal.
The module is based on BTS4880R chip.
The outputs are protected against overload, short circuit, overheating and voltage spikes when switching inductive loads.
Mounting

I/O modules are connected to the Wiren Board controller or to a WB-MIO, WB-MIO-E or WB-MGE v.3 interface converter on the right side via the side connector. Make sure all module pins are properly aligned with the mating connector. Secure the modules on the DIN rail using end stops on both sides, but leave approximately 2 cm of free space for easy removal when needed.
You can connect up to 8 modules in total: up to 4 input modules (type “I”) and up to 4 output modules (type “O”). Exception: only one WBIO-AI-DV-12 module can be connected.
Addresses are assigned sequentially. You can connect up to 4 modules in any order. If connecting more than 4, group modules by type: connect all of one type first, then the other.
Load connection
the module requires an external power supply to the terminals Vin and GND (11 to 45V).
The ground of the module must be connected to the ground of the controller!

Connecting to the controller
After physically connecting the module, it must be added to the controller configuration:
- In the web interface, go to Settings → Configuration files.
- Open the Extension modules and ports section and select the WBIO module (External I/O module) where the side-mounted WBIO module is connected.
- In the dropdown list Module type, select the type of the connected module.
- Click the Save button.
WBIO modules do not support hotplugging.
To remove a module, select the Not installed type.
Make sure the external module is visible in the web interface:
- Go to the Devices section.
- Find the Discrete I/O device for digital modules, or ADCs for analog modules. The channels will appear as EXTN_YYYY, where N is the module number and YYYY is the channel name.
The MQTT topic will be of the form /devices/wb-gpio/controls/EXTN_YYYY.
-
Configuration of a new side-mounted module
-
Channels of the external module in the Wiren Board web interface
Device revisions
Device images and drawings

Corel Draw 2018 (font — Ubuntu): WB-Library.cdr.zip
Visio:
- Wiren Board devices: WB-Visio-Lib.zip.
- Panels, circuit breakers, contactors, and more by a third-party developer.
Corel Draw PDF: Файл:WBIO-DO-HS-8.cdr.pdf
Autocad 2013 DXF: Файл:WBIO-DO-HS-8.dxf.zip
Autocad PDF: Файл:WBIO-DO-HS-8.pdf