Pinout

KNX extension module

When ordering the expansion module together with the controller are installed other terminals (pictured).

Terminal Function
O1 (Red) KNX (+)
O2 (n/a) n/a
O3 (Gray) KNX (-)

KNX connector

Configuration

You need to set the module type in the web interface, sectionConfigs => Hardware Modules Configuration: for Internal slot 1 (MOD1) or for Internal slot 2 (MOD2) depending on the KNX module position.

Configuration

Go to the console and install the packages wb-mqtt-knx (MQTT KNX Bridge), knxd, knxd-tools:

apt-get update

apt-get install knxd knxd-tools wb-mqtt-knx

After installation, you must edit the file /etc/default/knxd:

Replace the line:

DAEMON_ARGS="-u /tmp/eib -u /var/run/knx -i -b ip:"

with:

DAEMON_ARGS="-d /var/log/knxd.log -t 0xffe -f 9 -e 1.2.255 -E 1.1.10:30 -u /var/run/knx -i -b ncn5120:/dev/ttyAPP2 -D -T -R -S"


Decrypting keys:

Key Function
-d /var/log/knxd.log to go into the background and write to a log.
-e 1.1.255 assigns KNX-address knxd equal 1.1.255 as the IP gateway.
-E 1.1.10:30 specifies knxd to issue KNX addresses to nodes from the IP network in the range 1.1.10..1.1.30
-u /var/run/knx open local Unix socket
-t 0xffe set the output mask of debug messages.
-f 9 set max verbosity level
-i listen to the specified TCP port (default 6720). It is possible to register -i 6721 or other port. Not exclusive alternative -u
-b ncn5120:/dev/ttyAPP2 activate the ncn5120 driver on the port for MOD1 (when installing the module in the MOD 2 expansion slot, specify ttyAPP3)
-T -R activate gateway, tunnel mode (needed to work with ETS)
-D says knxd to announce themselves (Discovery) in the network
-S start the server (which responds to multicasts)

More detailed:

knxd --help

Operation

To start KNX daemon, you need to write a line in the console: service knxd start

Restart if necessary: service knxd restart

To check the status: service knxd status


All logs are stored in the file /var/log/knxd.log

When you receive a message from the KNX device, the data is published to the MQTT topic /devices/knx/controls/data in Wiren Board.

To control KNX devices you need to send commands to MQTT topic /devices/knx/controls/data/on.

An example of a command:

mosquitto_pub -h 192.168.0.10 -p 1883 -t /devices/knx/controls/data/on -m "g:0/0/1 GroupValueWrite 0x01"

Where:

-h 192.168.0.10 - IP-address of the controller with KNX

-p 1883 - MQTT port

-t /devices/knx/controls/data/on - MQTT topic for uploading information

-m "g:0/0/1 GroupValueWrite 0x01" - message for a KNX device

Learn more about working with KNX data:wb-mqtt-knx (MQTT KNX Bridge)


Script for wb-rules упрощающий обработку телеграмм: knx_group_addresses.js


When working with ETS, it's Important: in “interfaces” ETS, it's necessary to choose the interface of the PC through which communication occurs. Requesting knxd b by unicast (host ip address with daemon) does not allow to program the devices. In the illustration, the arrow indicates which method of interaction with ETS works:


EST Interface